7735BSP VORTEC AC Cooler Control Cabinet and Panel Cooling System with 35H Generator and Filter

Here you can order some of the original VORTEC products directly online through our online shop. Please note that the products listed in our shop represent only a fraction of the VORTEC products currently available! Feel free to contact us for a personal consultation and for quotes on the remaining VORTEC products and any questions you may have regarding compressed air technology, cooling, and cleaning with innovative compressed air solutions.

Description

Vortec A/C enclosure coolers come with a built-in mechanical thermostat. The temperature range is 27–32°C. No electrical connection or compressed air valve is required. The Vortec A/C model offers switchable continuous control cabinet ventilation of 84 liters per minute. It also features enhanced sound insulation (62 dBA). It is suitable for outdoor use. All models are UL listed and available in NEMA 12, NEMA 4, and NEMA 4X.

Compressed air-operated control cabinet cooling system with 733 watts cooling capacity
Air consumption 991l/min
Internal fixed thermostat (27°C to 32°C).
Overpressure outlet for warm air.
Purge air bypass
For NEMA Type 4 and 4X and similarly classified control cabinets.
With 3m cold air distribution kit and internal silencer.
External compressed air filter
IP56

You only need compressed air to operate the A/CTM – Systems!

They only need to drill a 48mm hole into the control cabinet housing!

Cold air intake and warm air outlet are ensured via this bore.

They experience no operational interruptions, as the systems are maintenance-free when using dry and filtered air!

Clean, cold air flows into the control cabinet housing at a slight overpressure (approx. 87 mbar), preventing dirt from entering. The warm air inside the cabinet is then released to the environment via a special valve design, also due to the overpressure. Overpressure can also be generated without cooling (4 mbar at 100 l/min).

The systems are weather and corrosion resistant.

The A/CTM – Systems cool reliably at ambient temperatures of up to 79°C

The advantages at a glance ACTM Conventional devices
Building volume 2.6 liters 52 to 85 liters
Installation time approx. 15 minutes 3 hours
Maximum ambient temperature 79°C 55°C
noise level 62 – 64 dB (A) 62 – 64 dB (A)
Optional continuous overpressure Yes No
guarantee 10 years 1 year

 

  Cooling capacity Air consumption
Model kcal/hour watt l/min
Nema 4/4X (IP56) Nema 12 (IP52)  
7715 7615 225 263 425
7725 7625 378 439 708
7735 7635 630 732 991
7770 7670 1263 1465 1981

 

Scope of delivery:  Cold air system, cold air connection kit, cold air silencer, self-draining 5µ compressed air filter